Continuous watts are what a station can hold, and surge watts are a short burst for starting motors. The Jackery Explorer 1000 v2 prints 3,000 W of surge against 1,500 W continuous. A 1/2 HP sump pump is listed at 1,050 W running and 2,150 W starting.

By the Power Station Chart team, checked against the documents listed at the end. How we review. Last reviewed October 31, 2026.

Starting spikeRunning wattsStation's continuous limitTime
The spike lasts a moment, but if it passes the station's surge figure, the station can shut off.

One pump, two readings of the starting figure

Honda's wattage guide lists a 1/2 horsepower sump pump at 1,050 running watts and 2,150 starting watts. Generac's generator brochure prints the same 2,150 under a column headed additional starting watts. Its worked example adds the largest starting figure to the total running watts.

On Honda's reading, the pump needs 2,150 W at the moment it starts. On Generac's, it needs 1,050 plus 2,150, or 3,200 W.

That difference decides whether a station fits. The Explorer 1000 v2 prints 3,000 W of surge. That clears 2,150 W and falls short of 3,200 W. Honda also marks both of its sump pump entries as needing 240 V. So a pump's own nameplate is the number to start from.

What stations print

Makers use their own words for the burst figure.

Bluetti's own FAQ calls the same 4,800 W Lifting Power and says it is for resistive loads only. That covers a narrower set of loads than a surge figure for a motor. EcoFlow lists X-Boost as a separate figure from surge on the DELTA 3. So surge, peak, boost and lifting power are four labels for figures that are not interchangeable. Jackery adds a time limit for the 2,000 W step on the 1500 Ultra, 15 minutes at most. It prints no time beside its 3,600 W surge figure.

Jackery Explorer 1000 v21,500 W continuous, 3,000 W surge
EcoFlow DELTA 31,800 W continuous, 3,600 W surge, 2,600 W X-Boost in the manual
Jackery Explorer 1500 Ultra1,800 W rated, 2,000 W for 15 minutes, 3,600 W surge peak
Bluetti Elite 3002,400 W continuous, 4,800 W labeled Surge Power in its spec sheet

Why a rating of 2x is common

Many stations print a surge figure at twice the continuous figure. The Explorer 1000 v2 lists 3,000 W against 1,500 W. The DELTA 3 lists 3,600 W against 1,800 W. The Explorer 300 v2 lists 600 W against 300 W.

A pump with a 2,150 W start and a 1,050 W run is itself close to a two-to-one ratio. That is why the starting figure, and not the running figure, usually decides whether a motor load fits.

Why compressors are the hard case

A refrigerator compressor draws far more at start than while running. Whirlpool's tech sheet lists compressors at 97 W and 104 W running. Their locked-rotor currents are 7.91 A and 11.35 A. At 115 V those currents work out to about 910 W and 1,305 W. Honda's guide puts a refrigerator or freezer start at 1,200 W.

A station that prints 300 W continuous and 600 W of surge sits below every one of those start figures. The Explorer 300 v2 is one such station. The running load of 86 to 104 W is about a third of its continuous rating, yet the start is higher than its surge. Locked-rotor current is the worst case, and a running start usually draws less.

Putting the numbers side by side

Compare the appliance's running watts with the station's continuous rating. Compare its starting watts with the surge rating, after deciding which reading of the starting figure the source uses. The runtime calculator does the first comparison and warns about the second. The method notes explain how startup figures and station peaks are lined up. A station can still shut off when a start load lands near its limit.

Products named above

FAQ

Is surge power the same as peak power?

The label varies by maker. Jackery says surge, some EcoFlow and Anker models say peak, and Bluetti uses both surge and lifting power for different cases. Check the footnote under each figure.

How long can a station hold its surge rating?

Makers rarely print one number. Jackery's 1500 Ultra lists 2,000 W for up to 15 minutes. Some Bluetti stations print tiers that range from a fraction of a second to 2 minutes.

Do motors in sump pumps and well pumps need surge headroom?

Plan for the larger reading until the pump's own label says otherwise. Generac lists a 1/2 horsepower well pump at 1,000 running watts and 2,100 additional starting watts.